Connect directly to any XR450 or XR5-SE Data Logger. Or connect to a recorder or data acquisition system's 0-5vdc input. No external power required.
Split core construction simplifies installation on existing conductor. Nylon thumb screws, no exposed metal parts; Monitor motors, pumps, or any AC load.
Input Current | AC Current, single phase, 50 - 400 Hz, load power factor 0.5 to 1.0 lead or lag. |
Accuracy (100 amp and higher models): | 1% of reading from 10% to 100% F.S. 3% of reading at 5% F.S. 5% of reading at 2% F.S. |
Temperature effect | Less than 0.05% from -20 to 55°C |
Temperature range | -20 to 55°C ( -4 to 131°F) |
Response time | 250 milliseconds, input from 10% to 90% of full scale, 200 amp and higher ranges. |
Ripple | 0.5% |
Voltage rating | 600 VAC tested with 2.5 KVDC for 60 seconds |
Overload | 1.6x full scale (continuous) |
Surge | 3x full scale |
Lead wires | 8 ft (2.4 meter) twisted 22 AWG, Black/Red per UL1015 |
Output signal | Linear 0 - 5 Vdc |
Output signal loading | 100k ohms or higher |
Low range usability | To below 0.1% of full scale |
Construction | ABS potted housing |
Environment | Indoor Type 1 rating per UL506 |
Size | 1.25 inches (32 mm) thick, Length and Width below |
Part No. | Range | Window Size | Length | Width | Price $US |
---|---|---|---|---|---|
SC20A | 0-20 amps AC | 0.5" square | 2.6" (66 mm) | 2.3" (59 mm) | 110. |
SC50A | 0-50 amps AC | 0.5" square | 2.6" (66 mm) | 2.3" (59 mm) | 107. |
SC100A | 0-100 amps AC | 0.5" square | 2.6" (66 mm) | 2.3" (59 mm) | 105. |
SC200A | 0-200 amps AC | 1" square | 3.3" (84 mm) | 3.0" (76 mm) | 105. |
SC500A | 0-500 amps AC | 2" square | 4.1" (104 mm) | 4.0" (102 mm) | 135. |
SC1000A | 0-1000 amps AC | 4" square | 6.1" (155 mm) | 6.0" (153 mm) | 165. |
SC1500A | 0-1500 amps AC | 2.5" square | 5.4" (137 mm) | 4.7" (120 mm) | 173. |